Sensor
Specifications
A non-invasive triaxial vibration and temperature sensor, epoxy-mounted to the transformer tank in about 15 minutes. No drilling, no outage, no connection to electrical or IT systems.
Hardware
DIA × H
50 × 25 mm
Weight
70 grams
BATTERY LIFE
10 years1
Material
Polycarbonate (UL-94
V0)
V0)
Temp Range
-40 °C to +80 °C
Battery Cert
UL1642
Compliance
RoHS, NEMA 250, ATEXZone 0/20
Ingress
IP69K
Functionality
Transmit Range
100 m
Sampling Freq
0–6.6 kHz (3.3 kHz typ.)
Measurements
Triaxial vibration + temperature
Reporting Range
4 samples/hr (typ.)
Scale
±16 g
Comm Cert
FCC / IC Part 15
Over-the-air (OTA) configurable
Auto-detect machine start
1 Normal use case with four transmissions per hour at ambient temperature.